220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Evaporator Model Number MM*35E MM*35E
Condensing Unit Model Number MC*35A MC*35A
FLA 47.9 18.9
with SCR Reheat
2
FLA 64.6 23.1
with Humidifier
FLA 29.3 12.9
with Electric Reheat and Humidifier
FLA 47.9 18.9
with SCR Reheat and Humidifier
2
FLA 71.0 26.8
* Specify disconnect or no disconnect
Notes:
1. Use MM*35E for MM*35K, except with SCR reheat.
2. SCR Reheat not available with MM*35K.
Table 9.9 Electrical data, 50Hz air-cooled systems using
single-point power kit, evaporator with direct-drive
blowers and indoor condensing unit (continued)
220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Unit Model Number MM*35E MM*35E
Condensing Unit Model Number MC*35A MC*35A
Cooling Only
FLA 27.1 10.4
with Electric Reheat
FLA 52.1 20.1
with SCR Reheat
3
FLA 68.8 24.3
with Humidifier
Table 9.10 Electrical data, 50Hz air-cooled systems using single-point power kit,
evaporator with belt-drive blowers and indoor condensing unit