220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Unit Model Number MM*35E MM*35E
Condensing Unit Model Number MC*35A MC*35A
FLA 33.5 14.1
with Electric Reheat and Humidifier
FLA 52.1 20.1
with SCR Reheat and Humidifier
3
FLA 75.2 28.0
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*35E for MM*35K, except with SCR reheat.
3. SCR Reheat not available with MM*35K.
Table 9.10 Electrical data, 50Hz air-cooled systems using single-point power kit,
evaporator with belt-drive blowers and indoor condensing unit (continued)
208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Unit
Model Number
MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Condensing Unit
Model Number
MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W
Cooling Only
FLA 14.8 19.9 12.7 16.6 14.8 7.8
WSA 17.8 24.2 15.3 20.2 17.8 9.4
OPD 25 40 25 30 25 15
with Electric Reheat
FLA 39.8 44.9 34.4 38.3 31.6 16.2
WSA 49.1 55.4 42.4 47.3 38.8 19.9
OPD 50 60 45 50 45 20
with SCR Reheat
2
FLA 44.0 61.6 38.0 52.7 38.9 19.9
WSA 54.3 76.3 46.9 65.3 47.9 24.5
OPD 60 80 50 70 50 25
with Humidifier
FLA 21.2 26.3 18.4 22.3 21.2 11.2
WSA 24.2 30.6 21.0 25.9 24.2 12.8
OPD 35 45 30 40 35 15
Table 9.11 Electrical data, 60Hz water/glycol-cooled systems using single-point power
kit, evaporator with direct-drive blowers and indoor condensing unit