220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Unit Model Number MM*35E MM*35E
Condensing Unit Model Number MC*35A MC*35A
FLA 33.5 14.1
with Electric Reheat and Humidifier
FLA 52.1 20.1
with SCR Reheat and Humidifier
3
FLA 75.2 28.0
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*35E for MM*35K, except with SCR reheat.
3. SCR Reheat not available with MM*35K.
Table 9.10 Electrical data, 50Hz air-cooled systems using single-point power kit,
evaporator with belt-drive blowers and indoor condensing unit (continued)
208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Unit
Model Number
MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Condensing Unit
Model Number
MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W
Cooling Only
FLA 14.8 19.9 12.7 16.6 — 14.8 — 7.8
WSA 17.8 24.2 15.3 20.2 — 17.8 — 9.4
OPD 25 40 25 30 — 25 — 15
with Electric Reheat
FLA 39.8 44.9 34.4 38.3 — 31.6 — 16.2
WSA 49.1 55.4 42.4 47.3 — 38.8 — 19.9
OPD 50 60 45 50 — 45 — 20
with SCR Reheat
2
FLA 44.0 61.6 38.0 52.7 — 38.9 — 19.9
WSA 54.3 76.3 46.9 65.3 — 47.9 — 24.5
OPD 60 80 50 70 — 50 — 25
with Humidifier
FLA 21.2 26.3 18.4 22.3 — 21.2 — 11.2
WSA 24.2 30.6 21.0 25.9 — 24.2 — 12.8
OPD 35 45 30 40 — 35 — 15
Table 9.11 Electrical data, 60Hz water/glycol-cooled systems using single-point power
kit, evaporator with direct-drive blowers and indoor condensing unit
Vertiv | Liebert Mini-Mate2—2 and 3 ton Technical Data Manual | 54