208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Unit
Model Number
MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Condensing Unit
Model Number
MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W
with Electric Reheat and Humidifier
FLA 39.8 44.9 34.4 38.3 — 31.6 — 16.2
WSA 49.1 55.4 42.4 47.3 — 38.8 — 19.9
OPD 50 60 45 50 — 45 — 20
with SCR Reheat and Humidifier
2
FLA 50.4 68.0 43.7 58.4 — 45.3 — 23.3
WSA 60.7 82.7 52.6 71.0 — 54.3 — 27.9
OPD 70 90 60 80 — 60 — 30
* Specify disconnect or no disconnect
Notes:
1. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
2. SCR Reheat not available with MM*24K or MM*36K.
Table 9.11 Electrical data, 60Hz water/glycol-cooled systems using single-point power
kit, evaporator with direct-drive blowers and indoor condensing unit (continued)
208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Evaporator
Model Number
MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Condensing Unit
Model Number
MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W
Cooling Only
FLA 21.2 26.3 16.8 20.7 — 16.8 — 8.5
WSA 24.2 30.6 19.4 24.3 — 19.8 — 10.1
OPD 35 45 25 35 — 30 — 15
with Electric Reheat
FLA 46.2 51.3 38.5 42.4 — 33.6 — 16.9
WSA 55.5 61.8 46.5 51.4 — 40.8 — 20.6
OPD 60 70 50 60 — 45 — 20
with SCR Reheat
3
FLA 50.4 68.0 42.1 56.8 — 40.9 — 20.6
WSA 60.7 82.7 51.0 69.4 — 49.9 — 25.2
OPD 70 90 60 70 — 50 — 30
Table 9.12 Electrical data, 60Hz water/glycol-cooled systems using single-point power kit,
evaporator with belt-drive blowers and indoor condensing unit
Vertiv | Liebert Mini-Mate2—2 and 3 ton Technical Data Manual | 55