Figure 3.1 Touchscreen Overview of a System with Rectifier On
Number Description
1 The On/Off button also acts as the Control button.
Table 3.1 Touchscreen Description
3.1.1 Single UPS - switching to Automatic operating mode
With the Trinergy™ Cube system in bypass, press the On/Off button (see Figure 3.1 above) to switch to automatic mode.
Enter the passcode in the pop up and then press Start in the control pop up to start the inverter.
The UPS starts in VFI mode and remains in this condition for a predetermined period, during which time the relevant
electrical characteristics are monitored. At the end of this period, which may last for several days depending on the
conditions being measured, Trinergy™ Cube selects the operating mode that will supply the load as efficiently as possible
without negatively affecting electrical characteristics such as power factor and current distortion.
Vertiv™ | Liebert® Trinergy Cube™ Operation and Maintenance Guide
14