VESDA by Xtralis VESDA VLF-500 Product Guide
www.xtralis.com 37
7 Factory Defaults
Parameter Allowed values Default values
Alert Smoke Threshold 1 & 2 0.025% - 2.0% obs/m*
(0.008% - 0.625% obs/ft.)
0.08% obs/m
(0.025% obs/ft.)
Action Smoke Threshold 1 & 2 0.025% - 2.0% obs/m*
(0.008% - 0.625% obs/ft.)
0.14% obs/m
(0.0448% obs/ft.)
Fire-1 Smoke Threshold 1 & 2 0.025% - 20% obs/m*
(0.008% - 6.25% obs/ft.)
0.2% obs/m
(0.0625% obs/ft.)
Fire-2 Smoke Threshold 1 & 2 0.025% - 20% obs/m*
(0.008% - 6.25% obs/ft.)
2.0% obs/m
(0.625% obs/ft.)
Alert Verification Delay 1 & 2 0 - 60 seconds 10 seconds
Action Verification Delay 1 & 2 0 - 60 seconds 10 seconds
Fire 1 Verification Delay 1 & 2 0 - 60 seconds 10 seconds
Fire 2 Verification Delay 1 & 2 0 - 60 seconds 10 seconds
Alarm Latching Enable Enabled or Disabled Enabled
Fault Latching Enable Enabled or Disabled Disabled
Airflow Major High Flow Fault 100% - 150% 130%
Airflow Major Low Flow Fault 50% - 100% 70%
Airflow Minor High Flow Fault 100% - 150% 120%
Airflow Minor Low Flow Fault 50% - 100% 80%
AutoLearn Smoke 15 min. 15 days 14 days
AutoLearn Flow 15 min. 15 days 14 days
Smoke Test Button Enabled or Disabled Disabled
Threshold set 1 and 2 Day (1) & Night (2) / Disabled Disabled
Table 7-1: Factory defaults
*For code-specific information, refer to Codes and Standards Information for Air Sampling Smoke Detection on page iii.
Note: If installing the detector as a UL compliant system the alarm signal connected to the control panel
for the fire evacuation shall not be less than 2.0 %obs/m (0.64 %obs/ft.).