028 -0427-15 _UI-V T8350_ A4 _ EN www.viconics.com June 2020
38
VT8350 [ User Interface Guide ]
Conguration Parameters Default Value Signicance and Adjustments
Deh. hysteresis
Default value: 5 % RH
Humidity Control Hysteresis
Used only if dehumidication sequence is enabled.
Range: 2 to 20% RH
Deh. max. cool.
Default value: 100%
Dehumidification Maximum Cooling Limit
Maximum cooling valve position when dehumidication is enabled. This can be
used to balance smaller reheat loads installed in regards to the capacity of the
cooling coil.
Range: 20 to 100%
Deh. lockout
Default value: Disabled
Dehumidification Lockout
Enables or disables dehumidication based on central network requirements
from the BAS front end.
Enabled: Dehumidication Authorized
Disabled: Dehumidication Not Authorized
Choices: Enabled or Disabled