VT8350 [ User Interface Guide ]
PARAMETER DETAILS
Conguration Parameters Default Value Signicance and Adjustments
Occupancy cmd
Default value: Occupied
Occupancy Command
Loc occ: occupancy is determined by local sequences (either PIR or schedule,
as congured under Occ. source).
Occupied: force occupied mode.
Unocc: force unoccupied mode.
Choices: Loc occ, Occupied or Unocc.
Schedule type
Default value: 7 days
Schedule Type
7 days: Independent scheduling identied by day of the week (Sunday -
Saturday)
5+1+1 days: Weekdays scheduling and Independent Weekend scheduling
identied as Weekdays, Saturday and Sunday
5+2 days: Weekdays scheduling and Weekend scheduling identied as
Weekdays and Weekend
Choices: 7 days, 5+2 days or 5+1+1 day
OPTIONS
The options settings allow the Room Controller to function in Occupied or Unoccupied mode following a dened Schedule type
set by the user.
6/7 Configuration
Language English
Units °C
Low backlight 60 %
Night backlight 5 %
RH display Disable
Options
Occupancy cmd Occupied
Schedule type 7 days