16b. If pressure in the diaphragm charge line does not drop, re-open
the diaphragm-charge-line ball valve, and proceed to the following
step.
17. If a Series 746-LPA Dry Accelerator is installed, close the ¼-turn
vent ball valve.
18. If a Series 746-LPA Dry Accelerator is installed, open the isolation
ball valve. This will set the accelerator.
19. Observe the system air pressure over a 24-hour period to confirm
system integrity. If there is degradation in system air pressure, find
and correct all leaks. NOTE: NFPA requires less than 1½-psi/
10-kPa/0.1-Bar leakage in 24 hours.
20. Open the water supply main drain valve.
CAUTION
Takeprecautionswhenopeningthewatersupplymaincontrol•
valve,sincewaterwillflowfromallopensystemvalves.
Failuretofollowthisinstructioncouldresultinpropertydamage.
Water Supply Main
Control Valve
21. Open the water supply main control valve slowly until water flows
steadily from the open water supply main drain valve.
I-768_16
FireLockNXT™DryValve
SERIES768
I-768INSTALLATION,MAINTENANCE,ANDTESTINGMANUAL
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_D

Table of Contents

Other manuals for Victaulic FireLock NXT 768 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Victaulic FireLock NXT 768 Series and is the answer not in the manual?

Victaulic FireLock NXT 768 Series Specifications

General IconGeneral
BrandVictaulic
ModelFireLock NXT 768 Series
CategoryControl Unit
LanguageEnglish

Related product manuals