EasyManua.ls Logo

Viessmann WB1A007 - Page 38

Viessmann WB1A007
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Connections
38
Electrical Connections
(continued)
Electrical connections to the power pump module
X2 X4 1 2 3 4X3 L N N L
120V
PUMP
RT
Note:
Boilers are factory shipped with
a wiring diagram (11”x17” page
inside a pouch) attached to the
inside of the front cover. The
wiring diagram shipped with the
boiler supercedes the wiring in-
formation in this manual.
Provide main power disconnect/service switch as per local code
requirements. Also refer to wiring diagram on page 71.
DHW
Legend
Main power supply
(120V, 60Hz, 1 PH).
Heating circuit pump (or boiler
pump with low-loss header
application). See DIP switch
selection setting S1 below. (Pump
runs for 10 seconds every 24
hours).
DHW tank temperature controller /
external heat demand
Room temperature thermostat
(Anticipator setting 0.2A)
DIP switch settings - S1
Remove short factory test leads from
terminal L, N and Ground before
connecting main power supply to
boiler.
Ensure that pressure activated by-pass
is installed with system layout 1 on
page 28.
Note:
If the boiler is operated using a 10VDC
modulating signal...
See separate OpenTherm (OT)
Module Installation
Instructions.
DIP switch settings - S1
Dip switch
number
Setting Explanation
1 OFF Pump B is ON during call
for heat. After call for heat
(RT-Terminal) is satisfied
pump B post-purges for
12 mins.
After DHW/external heat
demand (ST-Terminal) is
satisfied, pump B post-
purges for 1.5 minutes (see
important note above).
ON Pump B operates continu-
ously
2 OFF Do not adjust
3 OFF Do not adjust
4 OFF Do not adjust
5581 775 1.3
S1
Factory default settings
for S1 DIP switch
1 Dip switch S1
IMPORTANT
IMPORTANT

Related product manuals