Control Unit for Weather-Responsive Operation
with programming unit
(continued)
Overview of coding addresses (continued)
Coding (factory
default setting)
Address: Value
Function mode Coding
change
Address: Value
Possible change
0C6:000 Do not change
0C7:003 Resetting
to
summer/
winter time
Automatic 0C7:000
0C7:001
0C7:002
Manual resetting to s/w / date change blocked
Automatic resetting to s/w
Manual resetting to s/w / date change
released
0C8:001 External
switching
of heating
program
Contact open:
Space heating ON/domestic
hot water heating ON (ac-
cordingtotimeprogram)
Contact closed:
Central heating OFF/domestic
hot water heating OFF.
0C8:000 Contact open:
Central heating ON/domestic hot water
heating ON (according to time program)
Contact closed:
Continuous space heating ON/domestic hot
water heating ON (independent of preset time
program)
0C9:003 Startofsummertime:March 0C9:001
to
0C9:012
January
to
December
0D0:005 Start of summer time: Last week of
month
0D0:001
to
0D0:005
Week 1
to
Week 5 of selected month
0D1:007 Start of summer time: Last day of week
(Sunday)
0D1:001
to
0D1:007
Monday
to
Sunday
0D2:010 Startofwintertime: October 0D2:001
to
0D2:012
January
to
December
0D3:005 Start of winter time: Last week of
month
0D3:001
to
0D3:005
Week 1
to
Week 5 of selected month
0D4:007 Start of winter time: Last day of week
(Sunday)
0D4:001
to
0D4:007
Monday
to
Sunday
0D5:000 Program-
ming unit
Normal display format with
cover closed
0D5:001 Large display format for time and outdoor
temperature with cover closed
0D6:000 Program-
ming unit
Temperatures displayed in
”ºC” (º Celsius)
0D6:001 Temperatures displayed in ”ºF” (º Fahrenheit)
0D7:000 Do not change