VIKING TECHNICAL SUPPORT 1.800.908.0884
47
TROUBLESHOOTING - SOLAR ECU
# LED Status Meaning
Page 41
TS Ref#(s)
9 “C Loop” OFF Normal Condition.
SOLID An input from a device connected to the C Loop terminal. (pg 28, 32)
9, 10
10 “Open” OFF Normal Condition.
SOLID An input from a device to Exit, Fire, Strike or Open terminal. (pg 28, 32)
9, 10
11 “STOP” OFF Normal Condition.
SOLID Control Board is receiving an input from a device connected to the
Stop, UL or Re-Open terminals (pg 28, 32) 9, 10
FLASHING There is a problem with the required monitored sensor(s) connected to
the “UL” and/or “Re-Open” input terminals (pg 6-7, 22) 16, 20
12 “Close” OFF Normal Condition.
SOLID An input from a device connected to the Close terminal. (pg 28)
9, 10
13 “Siren”
OFF Normal Condition.
SOLID Second consecutive obstruction has been detected. (pg 24, 26)
1, 2, 11, 13
FLASHING Batteries are critically low.
1, 2
14 “Aux. Pwr”
OFF No voltage output on these terminals at the moment.(pg 19, 25)
SOLID There is 24V DC output on these terminals at the moment. (pg 19, 25)
15 “Diagnose” (Primary) OFF Normal Condition
FLASHING Errors have been detected; Check LCD Display for ERR messages. (pg 40)
16
“Close Limit” (Primary)
OFF Gate is not at the close limit position.
6, 22
SOLID Gate is at the close limit position.
21, 22
FLASHING Indicates a problem with the limit switches or wires.
6, 16
17
“Open Limit” (Primary)
OFF Gate is not at the open limit position.
6, 22
SOLID Gate is at the open limit position.
21, 22
FLASHING Indicates a problem with the limit switches or wires.
6,. 16
18 “ODS” OFF Normal Condition.
SOLID Obstruction event has been detected on the Primary motor. (pg 24, 26)
1, 2, 11, 13
FLASHING Overload event has been detected on the Primary motor. (pg 24, 26)
1, 2, 11, 13
19 “Timer” OFF If gate is at the open limit, the Timer to close is turned OFF. (pg 24)
SOLID Timer to close is ON and counting down to close the gate. (pg 24)
FLASHING Timer is ON but is not timing out due to a conicting command. (pg 24)
9, 10
S1 “Diagnose” (Secondary) OFF Normal Condition
FLASHING Errors have been detected; Check LCD Display for ERR messages. (pg 40)
SOLID Obstruction event has been detected on the Secondary motor. (pg 24, 26)
11, 13, 1, 2
RAPID FLSH Overload event has been detected on the Secondary motor. (pg 24, 26)
11, 13, 1, 2
S2
“Limit Close”
(Secondary)
OFF Secondary gate is not at the close limit position.
6, 22
SOLID Secondary gate is at the close limit position.
21, 22
S3
“Limit Open”
(Secondary)
OFF Secondary gate is not at the open limit position.
6, 22
SOLID Secondary gate is at the open limit position.
21, 22