PROBLEM POSSIBLE CAUSE TEST PROCEDURE-ACTION
Compressor kicks out on Air circulation on high side:
overload (continued)
a. Condenser or grille Clean condenser and air passage with vacuum
restricted by lint cleaner.
b. Condenser fan motor Disconnect fan motor leads and check separ-
Running or running ately. Replace motor if defective.
Slowly.
c. Condenser fan motor Put condenser fan motor top in place.
Top not in place.
Relay and / or overload Replace with parts known to be good.
Motor windings shorted Check windings with ohmmeter. See wiring
Diagram for resistance values. Replace
Compressor if motor is defective.
Over charge Check for high wattage and frosted suction
Line. Evacuate and recharge with correct
charge.
Freezer compartment too Thermostat:
warm. a. Set too warm Turn knob to higher setting.
b. Sensing tube not prop- See that sensing tube is properly positioned.
erly positioned
c. Out of calibration or Check thermostat for cut-in and cut-out
Not functioning temperatures. Replace if necessary.
Interior air circulation
a. Fan Check evaporator fan. Replace if defective.
b. Restriction in ducts Check for and remove obstruction in ducts.
Abnormal usage Instruct customer.
Bad door seal or door Adjust door to obtain proper seal.
not closing. Instruct customer to make sure door closes
completely.