n At interrupting gate control, the count process continuous with the
last recent counter value.
n At aborting gate control, the counter starts with the load value.
Limits Valid value range
Lower count limit
-2 147 483 648 (-2
31
)
Upper count limit
+2 147 483 647 (2
31
-1)
Interrupting gate control:
Aborting gate control:
Main counting direction forward
n The counter counts starting with the load value.
n When the counter reaches the end value -1 in positive direction, it
jumps to the load value at the next positive count pulse and the
gate is automatically closed.
n To restart the count process, you must create a positive edge of
the gate. The counter starts with the load value.
Limits Valid value range
Limit value
-2 147 483 647 (-2
31
+1)
to +2 147 483 647 (2
31
-1)
Lower count limit
-2 147 483 648 (-2
31
)
VIPA System SLIODeployment
Counter - Functions
HB300 | FM | 050-1BA00 | GB | 14-36 48