3. POWERMASTER-10 G2 INSTALLATION 
16 
D-304762 PowerMaster-10/30 G2 Installer's Guide 
 
3.8 Supplying Power to the Unit 
Connect power to the PowerMaster-10 G2 temporarily (see Figure 3.7a). Alternatively, you may power up from the 
backup battery, as shown in Figure 3.8. 
Disregard any “trouble” indications pertaining to lack of battery or lack of telephone line connection. 
For Europe Safety Compliance: 
a.  The model shall be installed according to the local electrical code. 
b.  The circuit breaker shall be readily accessible. 
c.   The rating of the external circuit breaker shall be 16A or less. 
d.  The cables for the AC mains connection shall have an overall diameter of 13mm and 16mm conduit. 
Please refer to Figure 3.7a "Power Cable Connection". 
 
Figure 3.8 – Connecting Power to the Control Panel 
Inserting Backup Battery: 
Connect battery pack as shown in 
Figure 3.8. 
1. Insert battery 
2. Connect the battery 
3.9 Closing the PowerMaster-10 G2 Control Panel 
Control panel final closure is shown below. 
 
Figure 3.9 - Final Closure 
To Close the Control Panel: 
1. Close the front cover 
2. Fasten the screws