5. PROGRAMMING 
D-304762 PowerMaster-10/30 G2 Installer's Guide 
67 
Option  Configuration Instructions 
 
enable (default) and disable 
13:ABORT ANOUNCE 
Here you determine that when the user disarms the system within the allowed abort interval a 
special beep will sound to indicate "no alarm transmission". 
 
enable (default) and disable 
5.15.6 OTHERS Setup 
13:OPERATION MOD   
⋅ ⋅ ⋅ 
 05:OTHERS SETUP    
Enter the "05:OTHERS SETUP" menu to configure its settings. 
Option  Configuration Instructions
 
01:DISARM OPTION 
Certain regulations require that when the system is armed in AWAY mode, it may not be 
disarmed from the outside of the house (such as by keyfobs) before entering the protected 
premises and activating an "Entry Delay" zone. To answer this requirement, the PowerMaster 
provides you with the following configurable options to disarm the system: 
A:  At "any time" (default), the system can be disarmed at all times from all devices. 
B:  During entry delay, the system can be disarmed only using keyfob or prox operated 
devices ("on entry wrless"). 
C:  During entry delay by code, the system can be disarmed only using PowerMaster panel 
keypad ("entry + away kp."). 
D:   During entry delay, the system can be disarmed using keyfobs or by code using the 
PowerMaster panel keypad ("on entry all.")..
 
03:END EXIT MODE 
The "Exit Delay" time can be further adjusted according to your preferred exit route. 
The control panel provides you with the following "Exit Mode" options: 
A:   "normal" (default) - The exit delay is exactly as defined. 
B:  "restart>reentry" - The exit delay restarts when the door is reopened during exit delay. 
The restart occurs once only. Restarting the exit delay is helpful if the user re-enters 
immediately after going out to retrieve an item that he left behind. 
C:   "end by exit" - The exit delay expires (ends) automatically when the exit door is closed 
even if the defined exit delay time was not completed.
 
 
Options: normal (default); restart>reentry and end by exit.
 
05:CONFIRM ALARM 
If two successive alarm events occur within a specific time window, the system can be 
configured to report the second alarm event as a "confirmed alarm" (see section 5.6.4 
option 61). You can activate this feature and set the respective time window. 
 
Options: disable (default in USA); in 30/45/60 (default)/90 minutes 
07:RPT CNFM ALRM 
Define whether the system will report a confirmed alarm. 
report disable (default) - The system will not report a confirmed alarm. 
report enable - The system will report a confirmed alarm. 
08:ENTRY DELAY 1 
09:ENTRY DELAY 2 
Two different entry delays allow the user to enter the protected site (while the system is in the 
armed state) via 2 specific doors and routes without causing an alarm.  
Following entry, the user must disarm the control panel before the entry delay expires. Slow-
rate warning beeps start sounding once the door is opened, until the last 10 seconds of the 
delay, during which the beeping rate increases. Locations No. 1 (entry delay 1) and 2 (entry 
delay 2) allow you to program the length of these delays.
 
 
Options : 00/15 (ENTRY DELAY 2 default)/30 (ENTRY DELAY 1 default)/45/60 seconds; 
3/4 minutes 
10:ABORT TIME 
The PowerMaster can be configured to provide a delay before reporting an alarm to the 
monitoring station (not applicable to alarms from FIRE, 24H SILENT and EMERGENCY 
zones). During this delay period, the siren sounds but the alarm is not reported. If the user 
disarms the system within the delay time, the alarm is aborted. You can activate the feature 
and select the "Abort Time" interval.
 
Options: in 00 (default in USA)/15/30(default)/45/60 seconds; in 2/3/4 minutes
 
11:CANCEL ALARM 
The  PowerMaster  can  be  configured  to  provide  a  ”Cancel  Alarm”  time  window  that  starts 
upon reporting an alarm to the Monitoring Station. If the user disarms the system within that