5. PROGRAMMING 
64 
D-304762 PowerMaster-10/30 G2 Installer's Guide 
Option  Configuration Instructions 
06:CONFIRM PANIC 
A confirmed panic alarm is reported if one of the following occurs within the confirmation time: 
a)  A second panic device is activated. 
b)  A second panic alarm on the same device is activated. 
c)  A tamper event is activated (not from the zone / device that initiated the panic alarm). 
 
Options: in 4/8/12/20 (default)/24 hours and disabled 
07:RPT CNFM ALRM 
Define whether the system will report a confirmed alarm. 
enable  +  bypass  (default)  -  The  system  will  report  a  confirmed  alarm  and  will  bypass  all 
alarmed open zones when the siren ends or when the confirmation timer expires. 
disable - The system will not report a confirmed alarm. 
enable - The system will report a confirmed alarm. 
08:ENTRY DELAY 1 
09:ENTRY DELAY 2
 
Two different entry delays allow the user to enter the protected site (while the system is in the 
armed state) via 2 specific doors and routes without causing an alarm.  
Following entry, the user must disarm the control panel before the entry delay expires. Slow-
rate warning beeps start sounding once the door is opened, until the last 10 seconds of the 
delay, during which the beeping rate increases. Locations No. 1 (entry delay 1) and 2 (entry 
delay 2) allow you to program the length of these delays. 
 
Options: 10/15/30(ENTRY DELAY 1 default)/45/60(ENTRY DELAY 2 default) seconds; 
3/4 minutes 
10:ABORT TIME 
The PowerMaster can be configured to provide a delay before reporting an alarm to the 
monitoring station (not applicable to alarms from FIRE, 24H SILENT and EMERGENCY 
zones). During this delay period, the siren sounds but the alarm is not reported. If the user 
disarms the system within the delay time, the alarm is aborted. You can activate the feature 
and select the "Abort Time" interval. 
 
Options: in 00 (default in USA)/15/30 (default)/45/60 seconds; in 2/3/4 minutes 
11:CANCEL ALARM 
The PowerMaster can be configured to provide a ”Cancel Alarm” time window that starts upon 
reporting an alarm to the Monitoring Station. If the user disarms the system within that "cancel 
alarm" time, a “cancel alarm” message is sent to the Monitoring Station indicating that the 
alarm was canceled by the user. 
 
Options: not active (default in USA); in 1/5 (default)/15/60 minute(s) and in 4 hours. 
 
5.15.4 DD243 Setup 
13:OPERATION MOD   
⋅ ⋅ ⋅ 
 03:DD243 SETUP   
Enter the "03:DD243 SETUP" menu to configure DD243 settings. 
Option  Configuration Instructions 
01:DISARM OPTION 
Define when it is possible to disarm the system: 
entry/wl+awy kp – By the control panel when the system is armed AWAY. By keyfob or 
keyprox during entry delay only. 
entry/all devs - During entry delay, when the system is armed AWAY, by all devices. When 
not in entry delay by keyfob or keyprox only. 
entry/DD devs (default) - During entry delay, when the system is armed AWAY, by using the 
keyfob or keyprox. Keypads cannot disarm at all. 
anytime/all dev – At any time and by all devices. 
02:ENTRY ALARM 
Define whether the system will report a confirmed alarm during an entry delay (see CONFIRM 
ALARM below). 
DD243 (default) - An alarm initiated by another detector during the entry delay is not regarded 
as a confirmed alarm. 
normal mode - The control panel will report a confirmed alarm for the second alarm that is 
triggered from a different zone within the confirmation time. There are no alarm restrictions 
during entry delay or for the delay zone.