6
Vivint Element CT200 Operation Guide
STAGING: Used for multiple stage systems only. Staging is the
number of degrees between the room temperature and
the target temperature at which the next stage in multi-
stage systems will engage to bring the room temperature
back to the target. The default is 2°F. The programmable
range is 2°F to 6°F (1°- 3°C).
CALIBRATION
1. From the Home screen, press
and hold the SIDE button for
three (3) seconds.
2. Press DOWN to highlight
Installer, then press the SIDE
button.
3. Press DOWN to highlight
Comfort, then press the SIDE
button.
4. Press DOWN to highlight
Calibration, then press the
SIDE button.The current
temperature oset displays.
5. Press UP or DOWN to change the value, then press the SIDE
button to conrm.
CYCLING
1. From the Home screen, press
and hold the SIDE button for
three (3) seconds.
2. Press DOWN to highlight
Installer, then press the SIDE
button.
3. Press DOWN to highlight
Comfort, then press the SIDE
button.
4. Press DOWN to highlight
Cycling, then press the SIDE
button. The current cycling value displays.
5. Press UP or DOWN to change the value, then press the SIDE
button to conrm.
Installer: Comfort Cont.
OFF TARGET
1.5°
HEAT/COOL
WHENEVER
-2°
CALIBRATION
OFFSET BY