EasyManua.ls Logo

VOKERA Compact A - Page 18

VOKERA Compact A
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
Fig. 19
HORIZONTAL TERMINATION ( g. 21)
The twin ue system must be converted to the dedicated con-
centric ue kit for termination.
The horizontal terminal is supplied with a built-in converter
box and cannot be shortened.
A 130mm hole is required for the passage of the concentric
terminal through the wall.
The air inlet pipe must always be level with or below, that of
the exhaust pipe.
Depending on site conditions it may be preferable to install the
terminal assembly prior to tting the twin ue pipes.
Mark and drill a level 130mm hole for the passage of the horizontal
ue terminal. Insert the terminal assembly into the ue hole.
Push- t the twin ue pipes onto the concentric to twin converter
box ensuring that the exhaust pipe connects to the exhaust
connection on the concentric to twin converter.
If necessary cut the plain ends (male) of the twin ue pipes to
allow connection to the concentric to twin converter.
NOTE
Before cutting twin ue pipes ensure allowances have been
made for connection onto the previous piece and onto the
concentric to twin converter. The last twin ue pipes must be
pushed 50mm onto the male spigots of the concentric to twin
converter.
NOTE
Seal the ue terminal assembly to the wall using cement or a
suitable alternative that will provide satisfactory weatherproof-
ing. The interior and exterior trim can now be tted.
VERTICAL TERMINATION ( g. 22)
The twin ue system must be converted to the dedicated con-
centric ue kit for termination.
The vertical terminal is supplied with a built-in converter box
and cannot be shortened.
INSTALLATION OF TWIN ADAPTOR KIT ( g. 19 & 20)
Insert the exhaust connection manifold (A) onto the appliance
ue outlet.
Remove the blanking plate (located to the left of the appliance
ue outlet) and – using the same screws – install the air inlet
plate (B).
Using the hole in the exhaust connection manifold as a guide,
drill a 3mm hole in the appliance ue spigot and secure the
exhaust manifold connection to the ue spigot using the screw
provided (C).
Using the two holes in the air inlet plate as a guide, drill a
3mm hole in each and secure the air inlet pipe/bend using
the screws provided.
The twin ue pipes extensions and accessories can now be
installed by pushing together (the plain end of each extension
or bend should be pushed approximately 50mm into the female
socket of the previous piece).
B
A
C
Fig. 20
A 130mm hole is required for the passage of the concentric
terminal through the ceiling and/or roof.
Depending on site conditions it may be preferable to install the
terminal assembly prior to tting the twin ue pipes.
Fit the appropriate ashing plate to the roof and insert the ver-
tical ue terminal through the ashing plate from the outside,
ensuring that the collar on the ue terminal ts over the ashing.
Push- t the twin ue pipes onto the concentric to twin converter
ensuring that the exhaust pipe connects to the exhaust con-
nection on the concentric to twin converter.
If necessary cut the plain ends (male) of the twin ue pipes to
allow connection to the concentric to twin converter.
NOTE
Before cutting twin ue pipes ensure allowances have been
made for connection onto the previous piece and onto the
concentric to twin converter. The last twin ue pipes must be
pushed 50mm onto the male spigots of the concentric to twin
converter.
You must ensure that the entire ue system is properly sup-
ported and connected.
Ensure that any horizontal sections of pipe have a fall of be-
tween 1 & 3º towards the appliance (1º =17mm per 1000mm).
Fig. 21
Fig. 22
1-deg = 17mm

Table of Contents

Related product manuals