Unit’digit:
0: single cycle then stop
1: single cycle then keep last speed
2: recycle
3: Plc reset when single cycle stop
Ten’s digit:
0:power off without saving
1:power off with saving
Hundred’digit:
0:stop without saving
1:stop with saving
0: Restart from the first stage; stop during
running (cause by the stop command, fault or
power loss), run from the first stage after
restart. 1: Continue to run from the stop
frequency; stop during running(cause by stop
command and fault), the inverter willrecord
the running time automatically, enter into the
stage after restart and keep the remaining
running at the setting frequency.
0.0~6553.5 unit depend on P42.21
Notice:Running time do not conclude
acceleration and deceleration time,same as
following