IR610 high performance vector control frequency inverter user manual Chapter6 Fault diagnosis and solutions
- 153-
Bit 12 of r27.10 indicates whether there is a warning message currently.
Warning
name
War
ning
code
Display
Reason
Measure
Insufficient
power
1
PoFF
1: The DC link voltage is insufficient
and cannot be started normally.
1:Check if the inverter power
supply is normal.
Wrong
parameter
2
A.PAR
A
1: The parameter settings are wrong,
such as:
The torque mode is set in the VF
control mode.
1:Modify and check theparameter
compatibility problem
Sleeping
status
5
SLEEP
1. The system is in a sleep state, and
the system will automatically start
when hibernation is over.
1:Generally no need to pay
attention to it
The warning code is used for the communication read warning type: when the communication
reads register r25.16, the contents of the returned register are the warning code.