EasyManua.ls Logo

Vortex IR610 Series - Page 49

Vortex IR610 Series
179 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 45-
Function
code
Parameter name
Description
Default
Property
1SVC(sensorless vector control)
Open loop vector without encoder
feedback and the feedback speed is
internally estimated and supports torque
control mode.
2VC Vector control with sensor
Close loop vec tor and torque control
supporting encoder feedback in high
precision or torque control
application.The inverter must be
equipped with a PG card that matches
the encoder. For the relevant parameters
of the PG card, please refer to P10 group
P00.05
Running mode
0Speed mode
1Torque mode
If use with DI function,19:Switch between
torque and speed Control and 20: torque
control diabled. Actuall effective running
mode is related with DI status
0
P00.06
Source of the
Operation Command
0keypad
1terminal
2communication
Command source: runstopforward
reversejogfast brake stop.etc
If use with DI function, 12Switching run
command to Keypad and 13Switching
run command to Communication,Actuall
effective command source is related with
DI status
0
P00.07
Numeric frequency
setting
00.00Hzmaximum frequency
50.00Hz
P00.08
Rotation direction
0Forward
1Reverse
It is only for keypad control to change
0