- 45-
Function
code
Parameter name
Description
Default
Property
1:SVC(sensorless vector control)
Open loop vector without encoder
feedback and the feedback speed is
internally estimated and supports torque
control mode.
2:VC Vector control with sensor
Close loop vec tor and torque control
supporting encoder feedback in high
precision or torque control
application.The inverter must be
equipped with a PG card that matches
the encoder. For the relevant parameters
of the PG card, please refer to P10 group
P00.05
Running mode
0:Speed mode
1:Torque mode
If use with DI function,19:Switch between
torque and speed Control and 20: torque
control diabled. Actuall effective running
mode is related with DI status
0
★
P00.06
Source of the
Operation Command
0:keypad
1:terminal
2:communication
Command source: run、stop、forward、
reverse、jog、fast brake stop.etc
If use with DI function, 12:Switching run
command to Keypad and 13:Switching
run command to Communication,Actuall
effective command source is related with
DI status
0
★
P00.07
Numeric frequency
setting
00.00Hz~maximum frequency
50.00Hz
☆
P00.08
Rotation direction
0:Forward
1:Reverse
It is only for keypad control to change
0
☆