IR610 high performance vector control frequency inverter user manual Chapter 5 function code table
- 82 -
P08.12
Output overcurrent
threshold
0.0%~300.0%
motor rated time
200.0%
☆
P08.13
Overcurrent detection
delay time
0.000~30.000s
Notice:When output current≥P08.12 and endure
P08.13 time,corresponding DO output effective
signal
0.100s
☆
When the output current is bigger than or over-limit detection point, lasts for longer than software over
current point detection delay time, DO terminal outputs ON signal.