24/7 Technical hotline - Ligne d’assistance technique - Línea de asistencia técnica
US 1.888.927.6333 / CA 1.888.592.7687
Specific wiring
Second sensor installation (2nd floor probe or exterior probe):
• Connectto1stwireofexternalsensor(2ndfloorsensor)toterminal2
• Connectto2ndwireofexternalsensor(2ndfloorsensor)toterminal3
Master/Relay installation (connecting 2 stats together):
• Connectfromterminal3onthe“master”toterminal3onthe“relay”thermostat.
• Connectfromterminal2onthe“master”toterminal2onthe“relay”thermostat.
NOTE:The“relay“thermostatwillnolongeruseitsownfloorsensorforthermalregulation.Itwillturn
on/off in tandem with the master thermostat.
Powering up
You can now power up the thermostat and begin the programming process. An easy to follow menu will
guide you through the programming. If you want to turn on / off the thermostat and heating system, hold
down the recessed button on the bottom of the stat for 3 seconds.
It is important to test the GFCI for correct installation and function. Testing can only be carried out while
the thermostat is calling for heat (see operating instructions for details).
When you have ensured that both the floor sensor ,heating elements and the GFCI are working correctly
you can complete the installation of floor covering and remove the protective cover on the front of the
thermostat.
POWERING UP & ERROR MESSAGES
Error messages
overload This will occur if more than 15 Amps have been connected to the thermostat
er1 This will occur if no floor sensor is detected
er2 This will occur if the floor sensor has a short circuit.
ground fault message This will occur if a ground fault is detected

Other manuals for Warmup 3IE