Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 8 WATER HEATER MANAGEMENT
OMM-0143_A GF-216 9/6/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 133 of 170
NOTES:
1. DO NOT press Auto-Stroke (Reset) button. Doing so may alter actuator calibration.
2. Depress and hold brass clutch button to manually rotate valve.
Figure 8.10.1-2: Actuator PC Board Components
CAUTION!
Power must be removed from the Actuator prior to attempting to disengage the clutch.
Failure to observe this precaution may damage the Actuator.
The PC board also contains a brass button which is used to disengage the clutch and permit the
ball valve to be manually rotated. To disengage the clutch, proceed as follows:
Actuator Clutch Disengagement Instructions
1. Disconnect the 4-pin connector on the Actuator to ensure that 24 VAC power is not being
supplied
2. Press and hold the brass CLUTCH button shown in Figure 8.10.1-2.
3. With the CLUTCH button depressed, the ball valve can be manually rotated from the fully
open (90°) to the fully closed (0°) position.
CLUTCH
(See Note 2)
POTENTIOMETER
AUTO-STROKE (RESET) BUTTON
DO NOT PRESS
(See Note 1)
DIP SWITCHES (4)
1OFF (DOWN)
2OFF (DOWN)
3ON (UP)
4OFF (DOWN)
TERMINALS (5)