Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 5 – SAFETY DEVICE TESTING
1. Set the Controller’s Enable/Disable switch to the Disable position.
2. Put the unit in Manual Mode by going to the Main Menu → Diagnostics → Manual Run
and setting the Manual Mode toggle to Enabled, then set the valve position between 25%
and 30%.
3. Remove the Air/Fuel Valve cover (see Figure 5.11-1) by rotating the cover counterclockwise
to unlock and lift up to remove.
4. Remove one of the two wires (#169 or #170) from the Ignition switch (Figure 5.11-2).
5. Initiate a unit start sequence.
6. The unit should begin its start sequence and then shut down and display Ign Switch Open
During Ignition.
7. Replace the wire on the Ignition switch and press the CLEAR button. The unit should
restart.
Figure 5.11-1: Typical Air/Fuel Valve Cover Location
Figure 5.11-2: Air/Fuel Valve Purge and Ignition Switch Locations
5.12 SAFETY PRESSURE RELIEF VALVE TEST
Test the safety Pressure Relief Valve in accordance with ASME Pressure Vessel Code, Section
VI.