Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3 OPERATION
OMM-0143_A GF-216 9/6/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 40 of 170
3.3.2 Calibration Menu
The Calibration menu contains the following sections and parameters:
Main Menu Calibration Combustion Calibration
NOx Requirement
Select
Select the unit’s NOx requirement: None, <= 20 or <= 9
PPM.
Valve Position - Target
Read Only
The unit’s target Valve Position.
Valve Position - Reading
Read Only
The unit’s actual Valve Position.
Blower Voltage - Target
Read Only
Target blower voltage for current Valve Position.
Blower Voltage - Reading
Read Only
The unit’s actual blower voltage.
O2% - Target
Read Only
The unit’s target O
2
% in the exhaust.
O2% - Reading
Numeric Entry
The unit’s actual O
2
% in the exhaust.
CO - Target
Read Only
The target CO amount in the exhaust, in ppm.
CO - Reading
Numeric Entry
The actual CO amount in the exhaust, in ppm.
NOx - Target
Read Only
The target NOx amount in the exhaust, in ppm
NOx - Reading
Numeric Entry
The actual NOx amount in the exhaust, in ppm.
Flame Strength - Reading
Numeric Entry
The unit’s Flame Strength, from Multimeter
Blower Speed - Target
Read Only
Target blower speed for current Valve Position.
Blower Speed - Reading
Read Only
Actual blower speed for current Valve Position.
Air Temperature - Reading
Read Only
The current air temperature.
Downstream Gas pressure
Numeric Entry
Appears only when fire rate = 100%.
Blower Voltage
Adjust
Adjust as needed to match targets to actual readings.
3.3.2.1 Main Menu Calibration Input/Output
Main Menu Calibration Input/Output Temperature Sensors
Sensor
Select
Select: Feed Forward, Exhaust, Outside Temp, Air
Inlet, Lower Inlet, Outlet.
Offset
Numeric Entry
Optional offset applied to current Sensor
Current Reading
Read Only
Current sensor’s current reading. (Flow In Adj & Flow
Rate removed ) .
Main Menu Calibration Input/Output Analog Inputs
Analog Name
Select
Select: Flow or Remote Analog In.
Offset
Numeric Entry
A correction value to selected input, if needed.
Current Reading
Read Only
Current reading of selected input.
Main Menu Calibration Input/Output Analog Outputs
Analog Name
Read Only
The name Analog Output.
Level
Numeric Entry
Set the output’s level (0.00 to 20.00 mA)
Offset
Numeric Entry
A correction value to the analog output, if needed.
3.3.2.2 Main Menu Calibration Subsystems
Main Menu Calibration Subsystems Air Fuel Valve
Valve Position
Manual Adjust
Set to desired Valve Position.
A/F Sensitivity
Numeric Entry
Set Air/Fuel Valve sensitivity (1% to 5%)
Main Menu Calibration Subsystems Spark Monitor