2.5.2 Automatic Float Vent Installation
All Innovation Water Heaters require an Automatic Float Vent connected to a Safety Check
valve. Both must be installed on all units, on the top of the heat exchanger dome, as shown
below. Both valves are included in the Accessory Kit shipped with the unit.
AUTOMATIC FLOAT VENT Instructions
1. All units are shipped with a hex nut in the center of the heat exchanger dome, which
protrudes through a hole in the center of the top enclosure panel. Remove this hex nut.
2. Fasten the Automatic Float Vent (P/N 99285) to top of the Service Check valve(P/N
99268), as shown below. Leave the red and black plastic caps in place on the Automatic
Float Vent.
3. Install the Service Check valve and Automatic Float Vent in place of the hex nut removed
instep 1.
Figure 2.5.2: Automatic Float Vent Installation
2.6 TEST HOSE CONNECTION
A test hose must be connected to the drain valve on the hot water outlet. This is required for
startup and testing (Figure 2.6). The test hose diameter should be a minimum of 3/4" (1.9 cm).
Figure 2.6: Test Hose Location
TO DRAIN
UPPER DRAIN
VALVE
HOT
WATER
OUT
TEST HOSE
AUTOMATIC FLOAT
VENT
SERVICE CHECK
VALVE