Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 2 – INSTALLATION
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 23 of 170
While observing the guidelines above, install the condensate trap as follows:
CONDENSATE TRAP INSTALLATION Instructions
1. Attach the 3/4” NPT nipple (P/N 94136) to the exhaust manifold’s drain port.
2. Loosen the condensate trap’s cap, then install it on the open end of the 3/4“ nipple.
3. Rotate the cap so the outlet faces towards the condensate drain, then tighten it.
4. Connect a length of 3/4” (1.91 cm) I.D. hose to the trap outlet. Use PVC, stainless steel,
aluminum or polypropylene for condensate drain piping. DO NOT USE carbon or copper
components
5. Route the hose from the trap outlet to a nearby floor drain and secure it with a hose clamp.
Figure 2.9-2: Sample Condensate Trap Installation – Left Side View
NOTE:
As a general guideline, AERCO recommends use of its Condensate Neutralizer Kit to raise
the pH level of the condensate prior to drainage. At a minimum, the installation must be
designed in accordance with local codes that specify acceptable pH limits. For more
information, see Technical Instruction Document TID-0029, Condensate Neutralization Kit
and TID-0074 Condensate Neutralization Tank.
Housekeeping pad should not extend
under the condensate assembly
3/4” NPT
NIPPLE
(P/N 94136)