Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 36 of 170
Figure 3.2: Edge Controller Front Panel Layout
The Soft-Keys on the Controller’s front face function as follows:
TABLE 3.2: Controller Front Panel Controls
Takes you to the previous screen.
Takes you to the touchscreen’s Main Menu (see Figure 1.2). If pressed
during a procedure, it aborts the procedure.
These buttons activate a selection box that can then be moved sequentially
through the editable/selectable parameters starting from top left (not the
title bar with home/previous icons) and moving right and then down as in
reading a book.
This button allows the editing of the parameter that is currently selected
through use of up/down arrows.
Multi-Function Bar, shows either:
• Fire Rate
• Valve Position
Parameter Indicator for both temperature
read-outs:
• LEFT: Inlet temperature or Setpoint
temperature
• RIGHT: Outlet temperature or
System Header temperature
Temperature scale indicator: Fahrenheit or
Celsius
Configurable temperature read-outs (2):
• LEFT: Inlet or Setpoint temperature
• RIGHT: Outlet or System Header
temperature
Operation Mode Indicators (2):
• LEFT: Demand or Manual
• RIGHT: Manager (BST only), COMM
when communicating
Edge Controller Touchscreen: see Section
1.8, below
Soft Keys: see table below
onAER Indicator Light
Fault Indicator Light
Low Water Level Test buttons (2):
• TEST: Initiates Low Water test
• RESET: Resets unit after Low Water
test