Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3 OPERATION
OMM-0143_A GF-216 9/6/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 44 of 170
3.3.4.1 Main Menu Advanced Setup Unit
Main Menu Advanced Setup Unit Unit Settings
Unit Serial #
Entry
The unit’s factory-set serial number. Do NOT change
except when replacing the Controller.
Unit Type
Enter
Displays unit’s product and model. Do NOT change
except when replacing the Controller.
Unit Size
Select
Displays the unit’s sizes. Do NOT change except when
replacing the Edge Controller.
Date
Numeric Entry
Allows you to set the current date.
Time Format
Toggle
Choose the 12 Hour or 24-Hour time format.
Time
Numeric Entry
Allows you to set the current time.
Exhaust Safety
Enable/Disable
Exhaust temperature shutoff function.
Fuel Type
Toggle
Choose Natural Gas
Control Type
Select
Specifies the controller type. Set to C-More only when
when replacing a C-More Controller.
Language
Select
Choose the language of the Controller’s display:
English, Spanish, French.
Unit of Measurement
Toggle
Choose unit of measure: Metric or English.
Temperature Sensor
Toggle
Specifies the sensor type: PT1000 or Balco. Do NOT
change unless replacing on a unit with a C-More
Controller and a Balco sensor.
Standby Pump On Time
Numeric Entry
The amount of time internal recirculation pump runs
when unit is in standby. Pump has a continual operation.
Standby Pump Off Time
Numeric Entry
The amount of time internal recirculation pump is
disabled during unit standby. Pump is continually cycled
during standby.
Post-Fire Pump Time
Numeric Entry
The amount of time internal recirculation pump runs after
unit has entered standby mode
Beeper
Toggle
Enables/disables the audible fault alarm.
Run Cycles
Numeric Entry
Displays number of run cycles since last system reset.
Can be reset to 0 or any number.
Run Hours
Numeric Entry
Displays the number of run hours since the last system
reset. Can be reset to 0 or any number.
Reset All Settings
Select Yes/No
Press Yes to reset all settings/restore default values.
Clear Fault Log
Select Yes/No
Press Yes to clear the Unit Event History.
Main Menu Advanced Setup Unit Front Panel Configuration
Upper Left Display
Select
Choose Setpoint or Water Inlet.
Upper Right Display
Select
Choose Water Outlet or System Header.
Multi-Function Bar
Select
Choose the Multi-Function Bar display: Fire Rate or
Valve Position.
Brightness
Numeric Entry
Adjusts Touchscreen brightness.
Screensaver Password
Enable/Disable
Determines if a Password is required to access the
Controller
Screen Timeout Minutes
Numeric Entry
Specifies touchscreen timeout in minutes (Screensaver
Password = Enabled).
Screen Timeout Now
Toggle
Choose Yes to put Controller into sleep mode.
(Screensaver Password = Enabled).
Main Menu Advanced Setup Unit Settings Transfer
Restore All Settings
Select
Restores all settings to the factory default.
Restore Common Settings
Select
Restores common settings to the factory default.
Save All Settings
Select
Saves all settings to USB or onboard memory.
Main Menu Advanced Setup Unit Fault Management