Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 6 MAINTENANCE
OMM-0143_A GF-216 9/6/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 80 of 170
Igniter-Injector Inspection/Replacement Instructions
VIEWED FROM BELOW, LOOKING UP
Figure 6.3-2: Igniter-Injector & Flame Detector Mounting Details
9. Torque the ignitor-injector to 15 ft-lbs. Do Not Over Tighten
10. Connect the ignition assembly to the gas injector tube of the igniter-injector by securing the
compression nut to the elbow of the ignition assembly.
11. Reconnect the igniter-injector cable and ground wire.
12. Reinstall the side and rear panels on the unit.
GAS INJECTOR TUBE
DO NOT POSITION THE GAS
INJECTOR TUBE WITHIN
THIS ARC
FLAME
OBSERVATION
PORT
FLAME
DETECTOR