12
IOM-S-Leak Defense 2211 2022-03-15 © 2022 Sentinel Hydrosolutions, LLC
THE WIRELESS CONTROL PANEL
Please call Technical Support at
866-410-1134 Option 2 so we can verify
and record proper calibration values,
to validate the warranty.
Note: Recommended Min mW should
be at or slightly above the mW when the
valve is closed. Max and Min should be
fairly far apart.
STEP 12:
Calibrate the system
DESIRED ACTION ON-SCREEN ACTIONS
Calibrating the Leak Defense System Main Screen
Navigating to the Calibration Screen Tap the Menu button.
Tap the Advanced button
Tap the Factory button
Type 65530 on the keypad, then tap the top right button (where it
displays this number)
Type 1 on the keypad, then tap the top right button
You are now in the Flow Calibration screen
Set No Flow Once the water has been turned OFF and you are on the Flow
Calibration screen, tap the Set No Flow button
Return to the main screen by tapping the Exit button
Set High Flow Once the water has been turned ON and you are on the Flow
Calibration screen, tap the Set High Flow button
Return to the main screen by tapping the Exit button
Turn off faucet, observe the flow arc, water % will lower to 0% after
several seconds
If it does not, you may have water running or a leak
The most common sources of flows that could be identified as leaks are leaky toilet flappers, leaking
seals in faucets, bad rubber washers in hose bibs (outdoor water hose spigots), and evaporative type
humidifiers.