EasyManua.ls Logo

Watts Vision BT-A02 RF - Page 11

Watts Vision BT-A02 RF
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 21
3.2.4 Water floor heating (multi zones) with several BT-M6Z02 RF
and only 1 boiler.
Equipments:
• 2 Connecting Boxes BT-M6Z02 RF
• 2 Thermostats BT-D02 RF (or BT-A02 RF or BT-DP02 RF)
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
Connect the actuators (eg. 22C – 22CX series) to the connecting boxes BT-M6Z02 RF
Connect the circulating pumps to the related connecting box BT-M6Z02 RF (*)
Connect both connecting boxes BT-M6Z02 RF to the heating relay of the boiler
VIRTUAL – RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF.
One thermostat can drive several zones.
3 ** OPTION - Pair the two BT-M6Z02: in this configuration, one BT-M6Z02 RF
(called “Main”) will centralize the information of the other BT-M6Z02 RF
(called “Sub”).
Refer to Centralized Installation of the user guide
BT-D02 RF
BT-D02 RF
1
st
floor
Ground floor
* In this application each BT-M6Z02 RF is connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL.
** In case of an installation with more than one BT-M6Z02 RF connecting box and only 1 circulating pump,
DIP SWITCH #1 Configuration: ON = GLOBAL on the BT-M6Z02 RF that drives the circulating pump
(= BT-M6Z02 Master) and NO NEED TO WIRE other BT-M6Z02 Slave to the heating relay of the boiler.
23
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
Connect the actuators (eg. 22C 22CX series) to the connecting boxes BT-M6Z02 RF
Connect the circulating pumps to the related connecting box BT-M6Z02 RF (*)
Connect both connecting boxes BT-M6Z02 RF to the heating relay of the boiler
VIRTUAL RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive
several zones.
3 ** OPTION - Pair the two BT-M6Z02: In this configuration, one BT-M6Z02-RF (called
Main) will centralize the information of the other BT-M6Z02-RF (calledSub).
Refer to Centralized Installation of the user guide
* In this application each BT-M6Z02 RF is
connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL.
** In case of an installation with more than
one BT-M6Z02 RF connecting box and only 1
circulating pump,
DIP SWITCH #1 Configuration: ON = GLOBAL
on the BT-M6Z02 RF that drives the circulating
pump (= BT-M6Z02 Master) and NO NEED TO
WIRE other BT-M6Z02 Slave to the heating
relay of the boiler.
23
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
Connect the actuators (eg. 22C 22CX series) to the connecting boxes BT-M6Z02 RF
Connect the circulating pumps to the related connecting box BT-M6Z02 RF (*)
Connect both connecting boxes BT-M6Z02 RF to the heating relay of the boiler
VIRTUAL RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive
several zones.
3 ** OPTION - Pair the two BT-M6Z02: In this configuration, one BT-M6Z02-RF (called
Main) will centralize the information of the other BT-M6Z02-RF (calledSub).
Refer to Centralized Installation of the user guide
* In this application each BT-M6Z02 RF is
connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL.
** In case of an installation with more than
one BT-M6Z02 RF connecting box and only 1
circulating pump,
DIP SWITCH #1 Configuration: ON = GLOBAL
on the BT-M6Z02 RF that drives the circulating
pump (= BT-M6Z02 Master) and NO NEED TO
WIRE other BT-M6Z02 Slave to the heating
relay of the boiler.
UP TO SIX
BT-M6Z02 RF
UP TO SIX
BT-M6Z02 RF