22 23
3.2.5 Water floor heating (multi zones) with several BT-M6Z02 RF
and only 1 boiler.
Equipments:
• 2 Connecting Boxes BT-M6Z02 RF
• 2 (or more) Thermostats BT-D02RF (or BT-A/DP02RF or
BT-D/DP02 RH RF ) **
• 1 Connecting box BT-HCM02 RF to drive the heating or cooling mode
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
•
Connect the actuators (eg. 22C – 22CX series) to the connecting boxes BT-M6Z02 RF
• Connect the circulating pumps to the related connecting box BT-M6Z02 RF
• Connect the Hot/Cool Module to the load (eg. A/C system) and to the heating relay of the
boiler
VIRTUAL – RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF.
One thermostat can drive several zones
3 Pair the two BT-M6Z02: In this configuration, one BT-M6Z02-RF (called “Main”)
will centralize the information of the other BT-M6Z02-RF (called “Sub”).
Refer to Centralized Installation of the user guide
4 Pair in slave mode the BT-HCM02 RF to the BT-M6Z02 RF master.
* In this application each BT-M6Z02 RF is connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL. In case of an installation with more than one BT-M6Z02 RF
connecting box and only 1 circulating pump, DIP SWITCH #1 Configuration: ON = GLOBAL on the
BT-M6Z02 RF that drives the circulating pump (= BT-M6Z02 Master)
** In application with humidity drier (for system limitation ref. to pag. 33) connect it to the output of Hot/Cool
module for triggering it on/off and managing relative humidity (%). In this case it is necessary to install at
least 1 thermostat BT-D02 RF with Humidity Sensor and locate it in a central area of the installation.
Note: one humidity drier per System – refer to SYSTEM LIMITATIONS (pag. 33).
BT-D02 RF
BT-D02 RF
25
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
• Connect the actuators (eg. 22C – 22CX series) to the connecting boxes BT-M6Z02 RF
• Connect the circulating pumps to the related connecting box BT-M6Z02 RF
• Connect the Hot/Cool Module to the load (eg. A/C system)
VIRTUAL – RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive
several zones
3 Pair the two BT-M6Z02: In this configuration, one BT-M6Z02-RF (called “Main”) will
centralize the information of the other BT-M6Z02-RF (called “Sub”).
Refer to Centralized Installation of the user guide
4 Pair in slave mode the BT-HCM02 RF to the BT-M6Z02 RF master
* In this application each BT-M6Z02 RF is
connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL.
In case of an installation with more than one
BT-M6Z02 RF connecting box and only 1
circulating pump,
DIP SWITCH #1 Configuration: ON = GLOBAL
on the BT-M6Z02 RF that drives the circulating
pump (= BT-M6Z02 Master)
** In application with humidity drier (for
system limitation ref. to pag. 34) connect it to
the output of Hot/Cool module for triggering it
on/off and managing relative humidity (%). In
this case it is necessary to install at least 1
thermostat BT-D02 RF with Humidity Sensor
and locate it in a central area of the
installation.
Note: one humidity drier per System – refer to
SYSTEM LIMITATIONS (pag. 34).
25
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
• Connect the actuators (eg. 22C – 22CX series) to the connecting boxes BT-M6Z02 RF
• Connect the circulating pumps to the related connecting box BT-M6Z02 RF
• Connect the Hot/Cool Module to the load (eg. A/C system)
VIRTUAL – RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive
several zones
3 Pair the two BT-M6Z02: In this configuration, one BT-M6Z02-RF (called “Main”) will
centralize the information of the other BT-M6Z02-RF (called “Sub”).
Refer to Centralized Installation of the user guide
4 Pair in slave mode the BT-HCM02 RF to the BT-M6Z02 RF master
* In this application each BT-M6Z02 RF is
connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL.
In case of an installation with more than one
BT-M6Z02 RF connecting box and only 1
circulating pump,
DIP SWITCH #1 Configuration: ON = GLOBAL
on the BT-M6Z02 RF that drives the circulating
pump (= BT-M6Z02 Master)
** In application with humidity drier (for
system limitation ref. to pag. 34) connect it to
the output of Hot/Cool module for triggering it
on/off and managing relative humidity (%). In
this case it is necessary to install at least 1
thermostat BT-D02 RF with Humidity Sensor
and locate it in a central area of the
installation.
Note: one humidity drier per System – refer to
SYSTEM LIMITATIONS (pag. 34).
25
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
• Connect the actuators (eg. 22C – 22CX series) to the connecting boxes BT-M6Z02 RF
• Connect the circulating pumps to the related connecting box BT-M6Z02 RF
• Connect the Hot/Cool Module to the load (eg. A/C system)
VIRTUAL – RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive
several zones
3 Pair the two BT-M6Z02: In this configuration, one BT-M6Z02-RF (called “Main”) will
centralize the information of the other BT-M6Z02-RF (called “Sub”).
Refer to Centralized Installation of the user guide
4 Pair in slave mode the BT-HCM02 RF to the BT-M6Z02 RF master
* In this application each BT-M6Z02 RF is
connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL.
In case of an installation with more than one
BT-M6Z02 RF connecting box and only 1
circulating pump,
DIP SWITCH #1 Configuration: ON = GLOBAL
on the BT-M6Z02 RF that drives the circulating
pump (= BT-M6Z02 Master)
** In application with humidity drier (for
system limitation ref. to pag. 34) connect it to
the output of Hot/Cool module for triggering it
on/off and managing relative humidity (%). In
this case it is necessary to install at least 1
thermostat BT-D02 RF with Humidity Sensor
and locate it in a central area of the
installation.
Note: one humidity drier per System – refer to
SYSTEM LIMITATIONS (pag. 34).
25
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
• Connect the actuators (eg. 22C – 22CX series) to the connecting boxes BT-M6Z02 RF
• Connect the circulating pumps to the related connecting box BT-M6Z02 RF
• Connect the Hot/Cool Module to the load (eg. A/C system)
VIRTUAL – RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive
several zones
3 Pair the two BT-M6Z02: In this configuration, one BT-M6Z02-RF (called “Main”) will
centralize the information of the other BT-M6Z02-RF (called “Sub”).
Refer to Centralized Installation of the user guide
4 Pair in slave mode the BT-HCM02 RF to the BT-M6Z02 RF master
* In this application each BT-M6Z02 RF is
connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL.
In case of an installation with more than one
BT-M6Z02 RF connecting box and only 1
circulating pump,
DIP SWITCH #1 Configuration: ON = GLOBAL
on the BT-M6Z02 RF that drives the circulating
pump (= BT-M6Z02 Master)
** In application with humidity drier (for
system limitation ref. to pag. 34) connect it to
the output of Hot/Cool module for triggering it
on/off and managing relative humidity (%). In
this case it is necessary to install at least 1
thermostat BT-D02 RF with Humidity Sensor
and locate it in a central area of the
installation.
Note: one humidity drier per System – refer to
SYSTEM LIMITATIONS (pag. 34).
25
For a correct installation, refer to dedicated user guides of each product, then:
WIRING CONNECTION:
• Connect the actuators (eg. 22C – 22CX series) to the connecting boxes BT-M6Z02 RF
• Connect the circulating pumps to the related connecting box BT-M6Z02 RF
• Connect the Hot/Cool Module to the load (eg. A/C system)
VIRTUAL – RF CONNECTION:
1-2 Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive
several zones
3 Pair the two BT-M6Z02: In this configuration, one BT-M6Z02-RF (called “Main”) will
centralize the information of the other BT-M6Z02-RF (called “Sub”).
Refer to Centralized Installation of the user guide
4 Pair in slave mode the BT-HCM02 RF to the BT-M6Z02 RF master
* In this application each BT-M6Z02 RF is
connected to a circulating pump.
DIP SWITCH #1 Configuration: OFF = LOCAL.
In case of an installation with more than one
BT-M6Z02 RF connecting box and only 1
circulating pump,
DIP SWITCH #1 Configuration: ON = GLOBAL
on the BT-M6Z02 RF that drives the circulating
pump (= BT-M6Z02 Master)
** In application with humidity drier (for
system limitation ref. to pag. 34) connect it to
the output of Hot/Cool module for triggering it
on/off and managing relative humidity (%). In
this case it is necessary to install at least 1
thermostat BT-D02 RF with Humidity Sensor
and locate it in a central area of the
installation.
Note: one humidity drier per System – refer to
SYSTEM LIMITATIONS (pag. 34).
BT-HCM02 RF
UP TO SIX
BT-M6Z02 RF
UP TO SIX
BT-M6Z02 RF