Frigo Top 10 - 43 | Pordoi 2000 - 4000 15
Label Description Range
Program level
1 2
did Digital input alarm delay: with i1F = EAL or i1F = bAL digital input alarm de-
lay: delay between the detection of the external alarm condition and its sig-
nalling.
With i1F = dor: door open signalling delay
With i1F = PAL: time for pressure switch function: time interval to calculate
the number of the pressure switch activation.
0 – 255min 2
nPS Pressure switch number: Number of activation of the pressure switch, dur-
ing the “did” interval, before signalling the alarm event (I2F = PAL).
If the nPS activation in the did time is reached, switch off and on the instru-
ment to restart normal regulation.
0 – 15 2
OdC Compressor and fan status when door open:
no = normal;
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF.
2
10.3.7 Other
Label Description
Program level
1 2
PbC Type of probe: it allows to set the kind of probe used by the instrument:
PbC = PBC probe,
ntC = NTC probe.
2
OnF On/Off key enabling:
no = disabled.
OFF = enabled.
ES = not set it.
2
dP1 First probe display. 1
dP2 Second probe display. 1
rEL Software release for internal use. 2
Ptb Parameter table code: read only. 2