Frigo Top 10 - 43 | Pordoi 2000 - 4000 16
10.4 Standard parameter settings
The standard parameter settings differ depending on the refrigerant. The tables below show the standard settings for refrigerant:
■
R134a
■
R134a and system with defrost
■
R404A
Making changes to these settings affects the functional safety of the system. Only make changes to the settings if you are familiar with
the outcome!
10.4.1 Regulation
Label Description
Refrigerant Program level
R134a R134a with defrost R404A 1 2
HY Differential 2 2 2 2
LS Minimum set point 0 0 -20 1
US Maximum set point 30 30 30 1
ot Thermostat probe calibration 0 0 0 2
P2P Evaporator probe presence y y y 1
oE Evaporator probe calibration 0 0 0 2
OdS Outputs delay at start up 0 0 0 2
db Dead band (neutral zone) n n n
y in case of
heating kit
2
AC Anti-short cycle delay 1 1 1 2
CCt Continuous cycle duration 0 0 0 2
CCS Set point for continuous cycle 0 0 0 2
COn Compressor ON time with faulty probe 15 15 15 2
CoF Compressor OFF time with faulty probe 30 30 30 2
10.4.2 Display
Label Description
Refrigerant Program level
R134 R134a with defrost R404A 1 2
CF Temperature measurement unit °C °C °C 2
rES Resolution dE dE dE 2
Lod Probe displayed P1 P1 P1 2
10.4.3 Defrost
Label Description
Refrigerant Program level
R134 R134a with defrost R404A 1 2
tdF Defrost type EL in in 2
dtE Defrost termination temperature 2 5 5 1
idF Interval between defrost cycles 1 3 3 1
MdF (Maximum) length for defrost 8 5 5 1
dSd Start defrost delay 0 0 0 2
dFd Displaying during defrost dEF dEF dEF 2
dAd MAX display delay after defrost 1 1 1 2
Fdt Draining time 1 1 1 1
dPo First defrost after start-up n n n 2
dAF Defrost delay after fast freezing 0 0 0 2