EasyManua.ls Logo

Weber SUMMIT SB38 S - Configuration Options

Weber SUMMIT SB38 S
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
Planning Ahead
Configuration Options
Recommended Gas Supply Locations
There are several configuration options for the grill
and gas supply access of your Island structure.
The 3 common options (A, B, C) are illustrated in the
‘Island’ Structure Configuration Options” table.
If there are local codes that apply to “built-in” gas
grills, you will have to conform to them. Installation
must conform with local codes or, in the absence of
local codes, with the National Code as applicable.
When using a gas supply system in an enclosure,
ventilation must be provided. Gas vapor is highly
explosive and can cause serious bodily injury or
damage to property if allowed to accumulate in a
confined space and ignited.
Recommended Construction Materials
We recommend that the construction and installation
of this grill is in a masonry structure and carried
out by a professional tradesperson. Masonry such
as stone or brick, and noncombustible countertops
such as marble or granite, is preferred. Other
noncombustible material along with metal studs may
also be used.
IMPORTANT: Wood or other combustible material
are not acceptable for the construction of the grill
structure.
NOTE: Contact your local municipality for building codes
regulating outdoor gas grill installations.
“ISLAND” STRUCTURE CONFIGURATION OPTIONS
C
B
A
1
1
1
2
2
2
“ISLAND” STRUCTURE CONFIGURATION OPTIONS
1
C
B
A
1
1
2
2
2
1 GENESIS 3-burner/4-burner grill
2 Gas supply
1 Built-In grill
2 Gas supply
Ventilation
Ventilation holes can be located in a low visibility
area and should be protected by screening material
to prevent rodents and insects from entering the
structure. Air holes will also help dry moisture.
NOTE: These drawings are only a reference.
Cross ventilation must be incorporated in the supporting
structure. We recommend a minimum of 100 square inches
(254 square cm) of venting per side.
Vents should be on two sides of the structure.
The drawings are for reference only.
Position the vents at both the bottom of the structure and
at the top of the structure.
The bottom vents should be as close to ground level as
possible. Make sure the vent area is not blocked by interior
supports of the structure.
We recommend vents with screens.
Access doors to the structure are not considered vents.
Clean the vents periodically.
m DANGER: Failure to follow recommended
minimum ventilation instructions can cause gas to
collect in the structure in the event of a gas leak.
This may result in a fire or an explosion which can
cause serious bodily injury or death, and damage
to property.
m WARNING: Ventilation openings must be provided
in the structure, with at least one mounted high
and at least one mounted low, to provide cross
ventilation in the event of a gas leak.
m WARNING: Keep the ventilation openings of the
enclosure free and clear of debris.

Related product manuals