CFW-10 - QUICK PARAMETER REFERENCE
Parameter Function
Adjustable Range
Factory
Unit User Setting Page
Setting
(1)
This parameter can be changed only with the inverter disabled (stopped motor).
(2)
This Parameter cannot be changed when the routine "load factory default" is excuted (P204=5).
V/F Control
P136
Manual Torque Boost
0.0 to 100 20.0 % 59
(IxR Compensation )
P137
Automatic Torque Boost
0.0 to 100 0.0
%
60
(automatic IxR Compensation)
P138 Slip Compensation 0.0 to 10.0 0.0 % 61
P142
(1) (2)
Maximum Output Voltage 0.0 to 100 100 % 62
P145
(1) (2)
Field weakening
P133 to P134 60.0
Hz
62
frequency (Fnom)
DC Link Voltage Regulation
P151 Actuation level of the voltage Model 100: 360 to 460 430 V 63
regulation at the DC Link Model 200: 325 to 410 380
(intermediary circuit)
Overload Current
P156
(2)
Motor Overload Current 0.3xInom to 1.3xInom 1.2xP295 A 64
Current Limitation
P169
(2)
Maiximum Output Current 0.2x1nom to 2.0x1nom 1.5xP295 A 64
CONFIGURATION PARAMETERS (P200 to P398)
Generic Parameters
P202
(1)
Control Mode
0 = Linear V/F Control
0- 65
1 = Quadratic V/F Control
P204
(1)
Load parameters with 0 to 4 = not used 0 - 66
Factory Setting 5 = Load Factory Default
6 to 999 = not used
P206 Auto-Reset Time 0 to 255 0 s 66
P208 Reference Scale Factor 0.0 to 100 1.0 - 66
P219
(1)
Starting point of the switching
0.0 to 15.0 15.0 Hz 66
frequency reduction
Local/Remote Definition
P221
(1)
Speed Reference 0 = HMI Keys / 0 - 67
Selection – Local Mode 1 = AI1
2 = E.P.
3 to 5 = Reserved
6 = Multispeed
P222
(1)
Speed Reference 0 = HMI Keys / 1 - 67
Selection – Remote Mode 1 = AI1
2 = E.P.
3 to 5 = Reserved
6 = Multispeed
P229
(1)
Command Selection 0 = HMI Keypad 0 - 67
Local Mode 1 = Terminals
P230
(1)
Command Selection 0 = HMI Keypad 1 - 67
– Remote Mode 1 = Terminals
P231
(1)
Forward/Reverse 0 = Forward 2 - 67
Selection 1 =Reverse
2 = Commands
Analog Inputs(s)
P234 Analog Input AI1 Gain 0.0 to 999 100 % 68
P235
(1)
Analog Input AI1 Signal
0 = (0 to 10) V/ (0 to 20)mA
0
-
69
1 = (4 to 20) mA
P236 Analog Input AI1 Offset -120 to 120 0 % 69
P248
Analog Input (AI1) Filter
0 to 200 200 ms 69
Time Constant