89
CHAPTER 9
TECHNICAL SPECIFICATIONS
This chapter describes the technical specifications (electrical
and mechanical) of the CFW-10 inverter series.
9.1 POWER DATA AC Input Specifications:
Voltage: -15%, +10% (with loss of motor efficiency)
Frequency : 50/60Hz (± 2 Hz)
Overvoltage: Category III (EN 61010/UL 508C)
Transient voltages according to Category III.
Minimum line impedance: variable according to inverter
model. Refer to Section 8.2.
Power-up: max. 10 ON/OFF cycles per hour.
9.1.2 Power Supply: 110-127V
Model: Current/Voltage(V)
Power (kVA)
(1)
Rated Output |Current (A)
(2)
Max. Output Current (A)
(3)
Power Supply
Rated Input Current (A)
Switching Frequency (kHz)
Max. Motor Power (cv)
(4) (5)
Dynamic Braking
Watt Losses (W)
Dimensions
(Height x Width x Depth)
Rheostatic Braking
1.6/
110-127
0.6
1.6
2.4
7.1
10
0.25HP/
0.18kW
40
2.6/
110-127
1.0
2.6
3.9
11,5
10
0.5HP/
0.37kW
45
9.1.1 Power Supply: 200-240V
132 x 95 x 121 mm
Model: Current(A)/Voltage(V)
Power (kVA)
(1)
Rated Output Current (A)
(2)
Max. Output Current (A)
(3)
Power Supply
Rated Input Current (A)
Switching Frequency (kHz)
Max. Motor Output (cv)
(4) (5)
Watt Losses (W)
Dimensions
(Height x Width x Depth)
Rheostatic Braking
1.6/
200-240
0.6
1.6
2.4
3.5
10
0.25HP/
0.18kW
30
2.6/
200-240
1.0
2.6
3.9
5.7
10
0.5HP/
0.37kW
35
4.0/
200-240
1.5
4.0
6.0
8,8
10
1HP/
0.75kW
50
132 x 95 x 121 mm
Single-Phase
7.3/
200-240
2.8
7.3
11
16
5
2HP/
1.5kW
90
1.61x115
x112mm
yes
no no no
Single-Phase
4.0/
100-127
1.5
4.0
6.0
17.7
10
1HP/
0.75kW
60
1.61x115
x112mm
yes
no no