8
Parameters Example (Optional HMI) (P219 = 1):
Soft Starter Data (Example)
Model: EXSSW070130T5SZ
Motor Data (Example)
Power: 75 HP
Rated Speed: 1770 RPM
Rated Current: 101A
Rated Voltage: 380 V
Service Factor: 1.15
• The following is a typical list of parameter changes needed using the Motor/Soft Starter data shown above.
P000=5 Parameter Access (5 = Password)
P219=1 Parameterization via keypad/ (trim pots and DIP switches) (1 = keypad)
P202=0 Type of Control (0 = Voltage Ramp)
P101=35 Initial Selected Voltage (35%)
P102=15 Voltage Ramp Time (15 seconds)
P400=380 Motor Rated Voltage (380 volts)
P401=77.7% Motor Rated Current (101 amps)
P406=1.15 Motor Service Factor (1.15)
P640=6 Thermal Motor Protection Class (Class 30)
• Local/Remote parameters allow the soft starter to be set up to operate from Keypad, Remote Terminal, or a
programmed combination of keypad and terminal inputs.
P220 – Local/Remote Selection
P229 – Local Status Command
P230 – Remote Status Command
• Read Only Parameters (P001 – P081) can be used for monitoring and troubleshooting. For a full list and
description please read the SSW07 Programming Manual. By monitoring certain read only parameters, the status
of inputs, outputs, and soft starter operational values can be determined without the use of any other test
equipment.
P003 - Motor Current
P006 - Soft Starter Status
P007 - Output Voltage
P012 - Digital Input Status
P013 - (Relay Output Status) – used to monitor relay outputs.