Output
Signal range (span) 0…20 mA
Programmable signal
ranges
0…20 / 4…20 / 20…0 and 20…4 mA
Load (max.) 4 mA / 600 / 12 V DC
Load stability ±0.01 % of span / 100
Sensor error detection 0 / 3.5 / 23 mA / none
Output limitation:
on 4…20 and 20…4 mA
signals
3.8…20.5 mA
on 4…20 and 20…4 mA
signals
0…20.5 mA
Current limit 28 mA
2-wire 4…20 mA Output
Signal range 4…20 mA
Load stability 0.01 % of span / 100
Load resistance (Vsupply-3.5) / 0.023 A []
Ext. 2-wire supply range 3.5…26 V DC
Effect of external 2-wire
supply voltage variation
< 0.005 % of span / V
Status Relay Output
Safe Area Zone 2 Installation
Voltage max. 125 V AC / 110 V 32 V AC / 32 V DC
Power max. 62.5 VA / 32 W 16 VA / 32 W
Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC
Common Specifications
Supply voltage, DC 19.2…31.2 V DC
Max. consumption 3.5 W (2 channels)
Fuse 400 mA / 250 V AC
Isolation voltage, test / operation:
Input / output / supply 2.6 kV AC / 250 V AC
Output 1 to output 2 1.5 kV AC / 150 V AC reinforced
Status relay to supply 1.5 kV AC / 150 V AC reinforced
Communication interface Programming front 4501