32 1066540000/00/02.09
Signal/Noise ratio Min. 60 dB (0…100 kHz)
Average response time incl. delay:
Temperature input 1 s
mA input 0.4 s
Calibration temperature 20…28 °C
Isolation Voltages, Test/Operation
Inputs/outputs/supply 2.6 kV AC/250 V AC
Output 1 to output 2 1.5 kV AC/150 V AC reinforced
Status relay to supply 150 V AC reinforced
Response time for cable fault <200 ms
Environmental Specifications
Ambient temperature –20…+60 °C
Storage temperature –20…+85 °C
Relative humidity <95 % (non-cond.)
Calibration temperature 20…28 °C
General Specifications
Communications interface configuration software, connection via CBX200
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP 20
Screw terminal torque 0.5 Nm
Vibration, IEC 60068-2-6 test Fc, 1g, 2…100 Hz
Vibration, continuous, IEC 60068-2-64 test Fh, 1g, 3…100 Hz
Wire Size AWG 26…14/0.13…2.08 mm² stranded wire
EMC immunity influence ±0.5 % of span
Extended EMC immunity:
Accuracy
General Values
Input Type Absolute Accuracy Temperature Coefficient
All ±0.1 % of span ±0.01 % of span / °C