Basic Values
Input Type Absolute Accuracy Temperature Coefficient
mA ±16 μA ±0.16 μA / °C
Pt100, Pt200, Pt1000 ±0.2 °C ±0.02 C / °C
Pt500, Ni100, Ni120, Ni1000 ±0.3 °C
±0.03 C / °C
Pt50, Pt400, Ni50 ±0.4 °C
±0.04 C / °C
Pt250, Pt300
±0.6 °C ±0.06 C / °C
Pt20
±0.8 °C ±0.08 C / °C
Pt10
±1.4 °C ±0.14 C / °C
TC type: E, J, K, L, N, T, U
±1 °C ±0.1 C / °C
TC type: R, S, W3, W5, LR
±2 °C ±0.2 C / °C
TC type: B 160…400 °C
±4.5 °C ±0.45 C / °C
TC type: B 400…1820 °C
±2 °
C ±0.2 C / °C
Default Settings
Input Type Temperature
Connection Type 3 wire
Temperature Unit °C
Temperature Sensor Type Temperature
PT Type PT 100
Output Parameters
Output Current Range 4…20 mA
Output Current on Error 23 mA
Analog Output Response
Time (1/10 s)
1