1066540000/00/02.09
41
896541 (ACT20X-SDI-HDO-H-S),
Ex barrier data channel 1, 11–14
Terminal
channel 1
U
m
:
VAC
U
o
:
VDC
I
o
:
mADC
P
o
W L
o
mH C
o
nF V
out
no load
V
out
with load
I
out
max.
IIA 20.8 2100 11.5 V 50 mA
IIB 10.8 640 9 V 60 mA
11–12
253 28 115 0.81
IIC 2.68 80
24 V
IIA 17.6 2100 12.5 V 50 mA
IIB 9.1 640 10 V 60 mA
11–13
253 28 125 0.88
IIC – –
24 V
IIA 15.1 2100 13.5 V 50 mA
IIB 7.8 640 11 V 60 mA
11–14
253 28 135 0.95
IIC – –
24 V
Status Relay Output
Safe area Zone 2 installation
Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC
Current max. 0.5 A AC / 0.3 A DC 0.5 AC / 0.1 A DC
Power max. 62.5 VA / 32 W 16 VA / 32 W
Common Specifications
Supply voltage 19.2…31.2 V DC
Max. consumption ≤ 3.5 W (2 channels)
Fuse 400 mA / 250 V AC
EMC immunity influence < ± 0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst < ± 1 % of span
Isolation Voltages, Test/Operation
Inputs/outputs/supply 2.6 kV AC / 250 V AC
Output 1 to output 2 1.5 kV AC / 150 V AC reinforced
Status relay to supply 1.5 kV AC / 150 V AC reinforced