50 1066540000/00/02.09
Relay Output
Relay functions Setpoint, Window,
Sensor error, Power and
Off
Hysteresis in % /
display counts
0.1…25 % / 1…2999
On and Off delay 0…3600 s
Sensor error detection Break / Make / Hold
Safe Area Zone 2 Installation
Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC
Power max. 500 VA / 60 W 64 VA / 60 W
Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC
Status Relay
Safe Area Zone 2 Installation
Voltage max. 125 V AC / 110 V DC 32 V AC / 30 V DC
Power max. 62.5 VA / 32 W 16 VA / 32 W
Current max. 0.5 A AC / 0.3 A DC 0,5 A AC / 1 A DC
Common Specifications
Supply voltage, DC 19.2…31.2 V DC
Max. consumption ≤ 3.5 W
Fuse 1.25 A / 250 V AC
Isolation voltage, test / operation 2.6 kV AC / 250 V AC
Communications interface CBX200 (Order no.: 8978580000)
Signal/Noise ratio Min. 60 dB (0…100 kHz)
Response time (0…90 %, 100…10 %):
Temperature input, programmable 1…60 s
mA / V input, programmable 0.4…60 s