EasyManua.ls Logo

Weidmüller ACT20X - Page 51

Default Icon
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1066540000/00/02.09
51
Isolation
Input to any 300 V AC double / reinforced isolation
Output relay to analogue output 150 V AC double / reinforced or
300 V AC basic isolation
Analogue output to supply 300 V AC double / reinforced isolation
Status relay to supply 150 V AC double / reinforced or
300 V AC basic isolation
Environmental Specifications
Ambient temperature –20…+60 °C
Storage temperature –20…+85 °C
Relative humidity < 95 % (non-cond.)
Calibration temperature 20…28 °C
General Specifications
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP 20
Screw terminal torque 0.5 Nm
Vibration, IEC 60068-2-6 test Fc, 1g, 2…100 Hz
Vibration, continuous, IEC 60068-2-64 test Fh, 1g, 3…100 Hz
Wire Size AWG 26…14 / 0.13…2.08 mm² stranded wire
EMC immunity influence ±0.5 % of span
Extended EMC immunity:
Accuracy
General Values
Input Type Absolute Accuracy Temperature Coefficient
All ±0.1 % of span ±0.01 % of span / °C