EasyManuals Logo

Weishaupt W-FM 200 User Manual

Weishaupt W-FM 200
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
94-228
6.9.7 Load range
LoadLimits
Param & Display RatioControl GasSettings
OilSettings
LoadLimits MinLoad_…
MaxLoad_…
In modulating operation, the load limits restrict the load range within the compound
curves programmed. On dual fuel burners, the load limits for each fuel can be set
separately.
Minimum load:
Parameter MinLoad_… limits the load range downward (partial load). Minimum
load can not be set below load point1, in conjunction with O2 trim not below load
point2.
Maximum load:
Parameter MaxLoad_… limits the load range upwards (full load).
0 % 100 %
P1
1
3
2
1 Minimum load MinLoad_…
2 Maximum load MaxLoad_…
3 Load range

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Weishaupt W-FM 200 and is the answer not in the manual?

Weishaupt W-FM 200 Specifications

General IconGeneral
BrandWeishaupt
ModelW-FM 200
CategoryController
LanguageEnglish

Related product manuals