6.9.7 Load range
LoadLimits
Param & Display RatioControl GasSettings
OilSettings
LoadLimits MinLoad_…
MaxLoad_…
In modulating operation, the load limits restrict the load range within the compound
curves programmed. On dual fuel burners, the load limits for each fuel can be set
separately.
Minimum load:
Parameter MinLoad_… limits the load range downward (partial load). Minimum
load can not be set below load point1, in conjunction with O2 trim not below load
point2.
Maximum load:
Parameter MaxLoad_… limits the load range upwards (full load).
1 Minimum load MinLoad_…
2 Maximum load MaxLoad_…
3 Load range