7 Commissioning
83054602 1/2020-01 La
45-96
7. Check start behaviour
For single stage operation only
If changing the ignition load setting ZL Gas, set limit switch ST1 to the same value
as ZL Gas.
Switch off and restart burner.
Check start behaviour and if necessary correct ignition position.
If the ignition position has been altered:
Re-check start behaviour.