REMOTE
PANEL
INSTALLATION
INSTALLER'S/OWNER'S RESPONSIBILITY
1.
Wiring
between
the
generator
set
and
either
a
remote
start
panel
or
remote
instrument
panel
must
comply
with
u.S.
Coast
Guard
Safety
Regulations
33
CFR-183.
2.
The
mimimum
voltage
required
at
the
starter
solenoid
is
9
volts.
3.
Therefore,
wire
gauges
from
TBl-l
to
TB3-l
and
from
TBl-2
to
TB3-2
should
be
selected
to
give
a maximum
voltage
drop
of
1
volt
or
less.
This
will
provide
9
volts
at
the
starter
solenoid
when
bat-
tery
terminal
voltage
is
down
to
10
volts,
indicative
of
a
deeply
discharged
battery.
Where
#16
wire
is
shown
in
the
table
of
Minimum
Wire
Gauges
below,
we
recommend
using
#14
wire
for
greater
strength
and/or
lower
voltage
drops.
MINIMUM
WIRE
GAUGES
(AWG)
Wire
Length
from
Generator
to
Remote
Panel
Terminals
0-16'
16-20'
20-25' 25-32'
32-40'
40-50'
50-65'
TB1-1
to
TB3-1
#12
#10 #10
#8
#8
#6
#6
TB
1-2
to
TB3-2 14 12 12
10
10
8
8
TB2-1
to
TB4-1
14 14 12 10
10
8
8
TB2-2
to
TB4-2
14 14 14 14
14 14
14
TB2-3
to
SENDER 14
14 14 14 14 14
14
TB2-4
to
SENDER 14 14 14 14
14 14
14
TB2-5
to
TB4-3
14 14 14 14
14 14
14
88