WHISPERKOOL SERIES ADVANCED CONTROLLER CONT.
Customer
Preference
Selection
Menu
(cont.)
CON/COF — Compressor on time (CON) and o time (COF) with a Probe 1 failure alarm:
These parameters are set at CON 40 minutes and COF 10 minutes. In the event that there
is a Probe 1 failure alarm, the compressor /refrigeration system automatically starts a
predetermined ON/OFF cycle, which is controlled by the CON and the COF parameters.
The customer can adjust these parameters to maintain the desired bottle probe temperature.
During a Probe 1 failure alarm, the bottle probe temperature can be monitored by pressing the
“Up” or “Down” arrow to view the temperature history.
HES — Dierential for Energy Reduction: This parameter is set at 4, which results in a set point
of 58°F during energy reduction. A decrease in this setting will decrease the set point, and an
increase in this feature will increase the set point.
ALARM CODES
Message Cause Output
“P1” Room probe failure Toggle “Con” and “COF” depending
on your temperature needs, if
necessary, or replace room probe
“P2” Evaporator probe failure Defrost end is timed
“HA” High temperature alarm Outputs unchanged
“LA” Low temperature alarm Outputs unchanged
“EA” External alarm Outputs unchanged